N-central Help

NetBotz Temperature service

The NetBotz Temperature service monitors the status and reported temperature, in Fahrenheit and Celsius of the specified temperature sensor.

This service cannot use Self Healing.

Service Type SNMP
Instances on a Device 68
Supported Systems/Applications Any NetBotz device that has an attached temperature sensor.
Device Class Other
Monitored By Windows probe
Scan Interval 5 minutes
Temperature Sensor

To determine the name of the temperature sensors attached to the NetBotz device, query the NetBotz device with the 1.3.6.1.4.1.5528.100.4.1.1.1.1 SNMP OID.

The default name is nbHawkEnc_0_TEMP.

OID/Calculation

Metric Name OID/Calculation Description
Temperature (\u00baC) 1.3.6.1.4.1.5528.100.4.1.1.1.8 The temperature reading in Celsius.
Temperature (\u00baF) 1.3.6.1.4.1.5528.100.4.1.1.1.9 The temperature reading in Fahrenheit.
Sensor Status 1.3.6.1.4.1.5528.100.4.1.1.1.3 An integer value representing whether the temperature sensor is connected or disconnected. The service transitions to a Failed state if the door switch reports a disconnected status.
Sensor Status Description 1.3.6.1.4.1.5528.100.4.1.1.1.3 A description of the sensor’s status.