APC PDU service

The APC PDU service monitors the phase status of the user-specified phase (circuit) and reports the low/medium/high thresholds for that sensor, as dictated by the PDU.

Service Type SNMP
Instances on a Device 3
Supported Systems/Applications Any APC PDU device that supports the PowerNet392 SNMP MIB.
Device Class Other
Monitored By Windows probe
Scan Interval 5 minutes
Phase Number Enter the phase number (1, 2, or 3) to monitor. The default is 1. The only asccepted values are 1, 2, or 3.

OID/Calculation

SolarWinds N-central services use Reverse Polish Notation (RPN) for all calculation formulae.

Metric Name

OID/Calculation

Load (Amperes) 1.3.6.1.4.318.1.1.12.2.3.1.1.2/ 10
Maximum Acceptable Load (Amperes) 1.3.6.1.4.318.1.1.12.2.2.1.1.4
Phase Utilization ((Load/10)/Maximum Acceptable Load)*100