N-central Help

APC UPS service

The APC UPS service provides basic and advanced APC UPS battery information.

Service Type SNMP
Instances on a Device 1
Supported Systems/Applications Any PowerNet-MIB Compliant Device from APC.
Device Class Server - Generic, Other, Printer, Scanner/Camera, Switch/Router, and Server - Windows.
>Monitored By Windows Probes
Scan Interval 15 minutes

OID/Calculation

Metric Name OID/Calculation Description
Status 1.3.6.1.4.1.318.1.1.1.2.1.1 The status of the UPS battery.
  • Unknown (1) : Warning
  • batteryNormal (2) : Normal
  • batteryLow (3) : Failed

A Battery Low (3) value indicates the UPS will be unable to sustain the current load, and its services will be lost if power is not restored.

Time On 1.3.6.1.4.1.318.1.1.1.2.1.2 The elapsed time since the UPS has switched to battery power.
Last Replaced 1.3.6.1.4.1.318.1.1.1.2.1.3 The date when the UPS system's batteries were last replaced, in mm/dd/yy format. For Smart-UPS models, this value is originally set in the factory. When replacing the UPS batteries, the administrator should reset this value.

Capacity

1.3.6.1.4.1.318.1.1.1.2.2.1 The remaining battery capacity expressed as a percentage.
Temperature 1.3.6.1.4.1.318.1.1.1.2.2.2 The current internal UPS temperature, expressed in degrees Celsius.
Time Remaining 1.3.6.1.4.1.318.1.1.1.2.2.3 The run time remaining before battery exhaustion.
Replace Indicator 1.3.6.1.4.1.318.1.1.1.2.2.4 Indicates if the UPS batteries need to be replaced.
  • noBatteryNeedsReplacing(1) : Normal
  • batteryNeedsReplacing(2) : Failed